Wire Size Calculator

Find the correct AWG wire gauge for your circuit based on current, voltage, distance, and maximum voltage drop. Supports copper and aluminum conductors.

Load current
System voltage
Panel to load (one direction)
NEC recommends ≤3%
Recommended Wire Size

Enter values above to find the right wire gauge.

Enter values above to calculate wire size.

Frequently Asked Questions

How do I determine wire size?

Consider three factors: (1) Ampacity — the wire must safely carry the current per NEC Table 310.16; (2) Voltage drop — should stay ≤3% for branch circuits; (3) Distance — longer runs need larger wire to keep voltage drop acceptable.

What size wire do I need for 30 amps?

Minimum 10 AWG copper or 8 AWG aluminum per NEC Table 310.16 (60°C). For runs over 50 feet at 120V, you may need 8 AWG copper to stay within 3% voltage drop.

Does wire length affect wire size?

Yes. Voltage drop is directly proportional to wire length. A 100-foot run may need a wire gauge 1–2 sizes larger than a 25-foot run for the same current and voltage drop target.

AWG Wire Size Reference Table

AWGDiameter (in)Max Amps (Cu, 60°C)Resistance (Ω/1000ft)
140.064153.14
120.081201.98
100.102301.24
80.128400.778
60.162550.491
40.204700.308
20.258950.194
1/00.3251250.122
2/00.3651450.0967
4/00.4601950.0608

Related Calculators

Wire ampacity from NEC Table 310.16 (60°C column). Resistance values from NEC Chapter 9, Table 8 at 75°C. Always consult a licensed electrician for actual installations.